The UniFi UPS 2U is a 2U rackmount line-interactive UPS managed from UniFi, rated 1500 VA / 1000 W, with 4 battery-backed and 4 surge-only C13 outlets and a field-replaceable 216 Wh battery.

It supports Graceful Shutdown for UNVR and UNAS, which needs UniFi OS 4.4.3 or later, and NUT for third-party devices. Output on battery is a simulated sine wave; the UPS 2U Pro adds pure sine wave output and a larger battery. It is 300 mm deep and weighs 13.7 kg, so check your rack depth and mounting rails.

Key features

  • 1500 VA / 1000 W, line-interactive, 230V
  • Up to 8 minutes at half load (500 W) and 2.3 minutes at full load
  • 4 x C13 battery backup/surge and 4 x C13 surge-only outlets, C14 inlet
  • 2 x 12V 9Ah lead-acid batteries, field-replaceable
  • 6 ms typical transfer time
  • 2 x GbE ports for surge in/out
  • 2U, 442.4 mm wide, 300 mm deep, 13.7 kg

Description

The UniFi UPS 2U is a 2U rackmount line-interactive UPS managed from UniFi, rated 1500 VA / 1000 W, with 4 battery-backed and 4 surge-only C13 outlets and a field-replaceable 216 Wh battery.

It supports Graceful Shutdown for UNVR and UNAS, which needs UniFi OS 4.4.3 or later, and NUT for third-party devices. Output on battery is a simulated sine wave; the UPS 2U Pro adds pure sine wave output and a larger battery. It is 300 mm deep and weighs 13.7 kg, so check your rack depth and mounting rails.

Key features

  • 1500 VA / 1000 W, line-interactive, 230V
  • Up to 8 minutes at half load (500 W) and 2.3 minutes at full load
  • 4 x C13 battery backup/surge and 4 x C13 surge-only outlets, C14 inlet
  • 2 x 12V 9Ah lead-acid batteries, field-replaceable
  • 6 ms typical transfer time
  • 2 x GbE ports for surge in/out
  • 2U, 442.4 mm wide, 300 mm deep, 13.7 kg

Specifications

Mechanical

Dimensions 442.4 x 300 x 87.4 mm
(17.4 x 11.8 x 3.4")
Weight 13.7 kg (30.2 lb)
Enclosure Material Galvanized steel
Form Factor Rack mount (2U)
Weatherproofing IP20

Hardware

Management Ethernet
Networking Interface (1) 100/10 MbE port for network connection
(2) GbE ports for surge in/out
Power (1) OVC II AC in: C14 socket, 1.8 m (5.9 ft) removable power cord
(4) Battery backup/surge protection: C13
(4) Surge protection: C13
Capacity 1,500VA/1,000W
Type Line interactive
Input Voltage Range 170–280V AC
Power Method (1) TN system, 220–240V AC, 10A Max., 50/60 Hz
Nominal Input Voltage 230V AC
Output Voltage 220–240V AC
Nominal Output Voltage 230V AC
Frequency Range AC mode: 50/60 Hz ±5 Hz (Auto sensing)
Battery mode: 50 Hz ±1 Hz
AC Voltage Regulation ±10% (Battery mode)
Transfer Time 6 ms typical; 10 ms max. (Battery mode)
Wave Form Simulated sine wave (Battery mode)
Battery Type (2) Lead Acid 12V, 9Ah
Runtime Full load: 2.3 min
Half load: 8 min
Battery Charging Time 6-8 hours recovery to 90% capacity
Overload at On-Line Mode 110% 5 min go to fault
120% go to fault immediately
Overload at Battery Mode 110% shutdown in 5 sec
120% shutdown immediately
Short Circuit Protection at On-Line Mode Breaker, 250V AC, 10A
Output Short-Circuit Current Ipeak 444.0A
Irms 223.1A
Buttons (1) Power
(1) Factory reset
LEDs Status: Off: device not turned on Flashing white: initializing / factory default Steady white: waiting for adoption Steady blue: device adoption and working Flashing blue: battery mode Alternating white/blue: firmware upgrading Rapid flashing blue: locate Steady red: warning Flashing red: low battery
Operating Altitude 3,000 m (1.9 mi)
Operating Environment Pollution Degree 2
Ambient Storage Temperature -20 to 50° C (-4 to 122° F)
Ambient Operating Temperature 0 to 40° C (32 to 104° F)
Ambient Operating Humidity 0 to 95% noncondensing
Certifications CE, IEC 62040-1